Electrical
Rated Voltage: 1500 VDC
Rated Current: 1200A, 2000A, or 4000A
Overcurrent Protection (Input): 80A – 630A
Maximum Overcurrent Protection (Main Output): 1200A, 2000A, or 4000A
Main Output Disconnect Switch Type: 1200A or 2000A Load Break Rated, 4000A Non-Load Break Rated
Maximum Number of Input-Side Dual-Fused Circuits (per cabinet): 8
SCCR: 100kA or 200kA
Input-Side Disconnect Options*: Six or eight 500A disconnects in a single-sided cabinet
Input-Side Contactor Maximum Current Option**: Up to 500A
Mechanical & Environmental
Nominal Enclosure Size (H x D x W)^2: 2100mm x 800mm x 800mm (82.7” x 31.5” x 31.5”) or 2100mm x 800mm x 2000mm ( 82.7” x 31.5” x 78.7”)
Enclosure Rating: NEMA 3R
Ambient Temperature Range: -40 to +50 ºC
Bus Bar Material: Tin-plated copper
Enclosure Material: Coated roll-formed steel
Cable Entry and Exit: Bottom feed only
*Special order, contact us for more details
**Single Cabinet dimensions: Fuse only design OR Fuse + Input-Side Contactor design.